Operating via a web browser within your own network

Value specification from:

This field indications how the control value used was determined.

Displayed Text

Explanation

Text

PMV_NONE

No control source.

PMV_CONFIG

The value is stored in the configuration.

PMV_MODE

The value can be determined by the reduction mode.

PMV_PR_PIGGY

The value comes from the PM (power reduction) input
(and is determined in combination with the matrix in the config-
uration or PM profile).

PMV_MPR_PIGGY

The value comes from the PM (power reduction) input of the
master (and is determined in combination with the matrix in the
configuration or PM profile).

PMV_MODBUS_1

The value comes from the ModBus PM V1 interface.

PMV_MODBUS_2

The value comes from the ModBus PM V2 interface.

PMV_PROFILE_ADAM

The value comes from the analog or digital input of the IO Box
(Adam Box).

PMV_PROFILE_INTERN

The value is specified in the PM profile.

PMV_ERROR

An error occurred while determining the value.

PMV_CONFIG_UTILITY

The value was determined via the internal configuration based
the Utility Meter measurement.

PMV_MODBUS_DM

The value comes from the ModBus DM interface (direct seller
interface).

Target power output %:

The fields indicates the percentage of the Plant's DC power determined by the control for the target out-

put.

The detailed values for the individual bus connections and for the total plant are displayed in the following

table below. The individual buses (RS485 A-C) are displayed depending on which bus is assigned to con-

trol the inverters.

The column

Total

always corresponds to the plant total and reflects the value from the grid connection

point. The consumption values are displayed in all of the columns, but only the plant total is taken into

account.

Note

!

The values from the individual inverters are calculated per bus and for the entire

plant.

Generator power (kW):

The generator power corresponds to the module output of the inverter that is connected to this data bus.

This value results from the total of the partial outputs entered in the field generator power under config-

uration | Devices | Configuration. This kW values is used when calculating the output reduction (e.g.: the

70% reduction).