Caution, Wall modules – Honeywell W7761A User Manual

Page 14

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

14

74-2699

CAUTION

When any device is energized by a Triac, the device must be able to sink a minimum of 25 mA.

NOTE: Triacs sink current to the 24 Vac common (COM terminal on the W7761A); see Fig. 19 for wiring example.

IMPORTANT:

If non-Honeywell motors, actuators, or transducers are to be used with Excel 10 Controllers, Triac compatibility must
be verified (see previous NOTE).

Wall Modules

The T7770A,B,C,D Wall Module sensor—(current feature that can be used with the Excel 10 W7761A RIO Device). See Fig. 6.

STANDARD
UTILITY
CONDUIT
BOX (2 X 4)
M OUNTING
HOLE S

K NOCKOUTS FOR EUROPE AN
A PPLIC ATIONS

3-5/32 (80)

2-3/8 (60)

29/32
(23)

5-1/16
(128)

2-3/8
(60)

T7770A1006

M15119

STANDARD
UTILITY
CONDUIT
BOX (2 X 4)
M OUNTING
HOLE S

K NOCKOUTS FOR EUROPE AN
A PPLIC ATIONS

3-5/32 (80)

2-3/8 (60)

1-1/4
(32)

5-1/16
(128)

2-3/8
(60)

T7770C

70

65

60

55

85

80

75

DIP

Switch S4 Settings:

1,3,5=on; 2,4=of

f 2,4=on; 1,3,5=of

f 1,2,3,4=on; 5=0f

f

W7753

XL600-XL20

W7752

LED RETURN

BYP

ASS

LED

FA

N

SETPT

SENSOR

GND

LED

SETPT

SENSOR

AL

COM

LED

SETPT

SENSOR

GND

BYP

ASS/F

AN

BYP

ASS/F

AN

9 8 7 6 5 4 3 2 1

E-BUS

E-BUS

Fig. 6. T7770A,B,C,D (T7770A,C shown) construction in in. (mm), sensor—(current feature that can be used with RIO

Device).