EXCEL 10 W7761A INPUT/OUTPUT DEVICE

73

74-2699

Table E-2 lists the points for Sensor Resistance versus Temperature. Fig. E-2 shows the graph of these points.

Table E-2. Sensor Resistance Versus Temperature.

°F (°C)

Resistance Ohms

30 (-1.1)

1956.79

35 (1.7)

1935.79

40 (4.4)

1914.79

45 (7.2)

1893.79

50 (10)

1872.79

55 (12.8)

1851.79

60 (15.6)

1830.79

65 (18.3)

1809.79

70 (21.1)

1788.79

75 (23.9)

1767.79

80 (26.7)

1746.79

85 (29.4)

1725.79

90 (32.2)

1704.78

95 (35)

1683.78

100 (37.8)

1662.78

105 (40.6)

1641.78

110 (43.3)

1620.78

115 (46.1)

1599.78

120 (48.9)

1578.78

1650

1600

1550

1500

1700

1750

1800

1850

1900

1950

2000

55

50

45

40

35

30

60 65 70 75 80 85 90 95 100 105 110 115 120

OHMS

°

F

SENSOR RESISTANCE VERSUS TEMPERATURE

M11960

23.9

21.1

18.3

15.6

12.8

10

7.2

4.4

1.7

-1.1

26.7

29.4

32.2

35

40.6

46.1

37.8

43.3

48.9

°

C

Fig. E-2. Graph of Sensor Resistance versus Temperature.

Sensor Type:
T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and C7770A.

Sensor Use:
Space Temperature and Discharge/Return Air Temperature.

Table E-3 lists the points for Sensor Resistance versus Temperature. Fig. E-3 shows the graph of these points.

Table E-3 Sensor Resistance Versus Temperature.

°F (°C)

Resistance Ohms

40 (4.4)

9961.09

45 (7.2)

9700.90

50 (10)

9440.72

55 (12.8)

9180.53

60 (15.6)

8920.35

Advertising