Table 8. Excel 10 W7761A Device Ordering Information (Continued).

Part Number

Product Description

Comments

Accessories (Continued):

ML6474A1008

Direct Coupled Actuator, 132 lb-in. torque, Series 60

ML6185A1000

Direct Coupled Actuator, 50 lb-in. spring return

Series 60

EL7680A1008

Wall Mounted Wide View Infrared Occupancy Sensor

EL7628A1007

Ceiling Mounted Infrared Occupancy Sensor

EL7611A1003,
EL7612A1001

Ultrasonic Occupancy Sensors

EL7630A1003,
EL7621A1002,
EL7621A1010

Power Supply/Control Units for Occupancy sensors

C7400A1004

Solid State Enthalpy Sensor (4 to 20 mA)

For outdoor and return air enthalpy

C7600B1000

Solid State Humidity Sensor (2 to 10 V)

For outdoor and return air humidity

C7600C1008

Solid State Humidity Sensor (4 to 20 mA)

For outdoor and return air humidity

C7600C1018

Solid State Humidity Sensor (2 to 10 V)

For outdoor and return air humidity

MMC325-010,
MMC325-020

Pneumatic Retrofit Transducers.
Select pressure range: (010) 0 to 10 psi (68.97 kPa)
or (020) 0 to 20 psi (137.93 kPa).

Use to control Pneumatic reheat valves

MMCA530

DIN rail adapter for MMC325 Transducers

MMCA540

Metal enclosure for MMC325 Transducers

ML7984B3000

Valve Actuator Pulse Width Modulation (PWM)

Use with V5011 or V5013 F and G Valves

ML6161B1000

Damper Actuator Series 60

M6410A

Valve Actuator Series 60

Use with V5812/V5813 Valves

ML684A1025

Versadrive Valve Actuator with linkage, Series 60

Use with V5011 and V5013 Valves

ML6464A1009

Direct Coupled Actuator, 66 lb-in., Series 60

ML6474A1008

Direct Coupled Actuator, 132 lb-in. torque, Series 60

ML6185A1000

Direct Coupled Actuator, 50 lb-in. spring return

Series 60

V5812A

Two-way terminal unit water valve; 0.19, 0.29, 0.47,
0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or

2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off
rating for 0.19 to 1.9 Cv is 65 psi; for 2.9

and 4.9, Cv is 45 psi. (Coefficient of

volume or capacity index Cv = gallons per

minute divided by the square root of the
pressure drop across the valve.)

V5813A

Three-way mixing terminal unit hot water valve; 0.19,
0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm)

or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off
rating 0.19 to 0.74 Cv is 55 psi; 1.2, and

1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi.

R8242A

Contactor, 24 Vac coil, DPDT

AT72D, AT88A, AK3310, etc. Transformers

EN 50 022

DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)

Obtain locally: A controller requires 5 in.

Augat Inc. part number 2TK2D DIN rail (adapter)

Purchase from Augat Inc. two DIN rail
adapters for each controller

Serial Interface Cable, male DB-9 to female DB-9 or
female DB-25.

Obtain locally from any computer
hardware vendor.

Cabling

Honeywell AK3791 (one
twisted pair) AK3792 (two
twisted pairs)

E-Bus (plenum): 22 AWG (0.34 mm

2

) twisted pair

solid conductor, nonshielded or Echelon

approved

cable.

Level IV 140°F (60°C) rating

Honeywell AK3781 (one
twisted pair) AK3782 (two
twisted pairs)

E-Bus (nonplenum): 22 AWG (0.34 mm

2

) twisted pair

solid conductor, nonshielded or Echelon

approved

cable.

Level IV 140°F (60°C) rating

Honeywell AK3725

Inputs: 18 AWG (1.0 mm

2

) five wire cable bundle

Standard thermostat wire

(continued)

Advertising