EXCEL 10 W7761A INPUT/OUTPUT DEVICE

67

74-2699

Table C4. Configuration Parameters (Left Continued).

Engineering Units:

English (Metric) or

Digital

State

or

Value

of

User Address

NvName

Field Name

States plus Range

State

Default

DO5FlSpeed

nciFloatConfig

DO4

seconds
0 to 900

90

DO6FlSpeed

nciFloatConfig

DO5

seconds
0 to 900

90

DO7FlSpeed

nciFloatConfig

DO6

seconds
0 to 900

90

DO8FlSpeed

nciFloatConfig

DO7

seconds
0 to 900

90

DO1PWMPeriod

nciPWMConfig1

DO0.si_period_pwm

seconds
0.0 to 3000

25.6

DO1PWMZero

nciPWMConfig1

DO0.si_pnct_time

seconds 0.0 to 3000

0.1

DO1PWMFull

nciPWMConfig1

DO0.si_delta_time

seconds 0.0 to 3000

25.5

DO2PWMPeriod

nciPWMConfig1

DO1.si_period_pwm

seconds 0.0 to 3000

25.6

DO2PWMZero

nciPWMConfig1

DO1.si_pnct_time

seconds 0.0 to 3000

0.1

DO2PWMFull

nciPWMConfig1

DO1.si_delta_time

seconds 0.0 to 3000

25.5

DO3PWMPeriod

nciPWMConfig1

DO2.si_period_pwm

seconds 0.0 to 3000

25.6

DO3PWMZero

nciPWMConfig1

DO2.si_pnct_time

seconds 0.0 to 3000

0.1

DO3PWMFull

nciPWMConfig1

DO2.si_delta_time

seconds 0.0 to 3000

25.5

DO4PWMPeriod

nciPWMConfig1

DO3.si_period_pwm

seconds 0.0 to 3000

25.6

DO4PWMZero

nciPWMConfig1

DO3.si_pnct_time

seconds 0.0 to 3000

0.1

DO4PWMFull

nciPWMConfig1

DO3.si_delta_time

seconds 0.0 to 3000

25.5

DO5PWMPeriod

nciPWMConfig2

DO4.si_period_pwm

seconds 0.0 to 3000

25.6

DO5PWMZero

nciPWMConfig2

DO4.si_pnct_time

seconds 0.0 to 3000

0.1

DO5PWMFull

nciPWMConfig2

DO4.si_delta_time

seconds 0.0 to 3000

25.5

(continued)