Honeywell W7761A User Manual

Page 78

Advertising
background image

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

78

74-2699

Sensor Type:
T7242 or equivalent.

Sensor Use:
CO

2

concentration.

Table E-9 lists the points for Sensor Voltage versus CO

2

concentration. Fig. E-9 shows the graph of these points.

Table E-9. Sensor Voltage Versus CO

2

Concentration.

CO

2

Concentration PPM

Sensor Voltage

0

0.00

100

0.50

200

1.00

300

1.50

400

2.00

500

2.50

600

3.00

700

3.50

800

4.00

900

4.50

1000

5.00

1100

5.50

1200

6.00

1300

6.50

1400

7.00

1500

7.50

1600

8.00

1700

8.50

1800

9.00

1900

9.50

2000

10.00

0

1

2

3

4

5

6

7

8

9

10

100

300

500

700

900

1100

1300

1500

1700

1900

200

400

600

800

1000

1200

1400

1600

1800

2000

VOLTS

PPM

SENSOR VOLTAGE VERSUS CO2 CONCENTRATION

M11611

Fig. E-9. Graph of Sensor Voltage versus CO

2

concentration.

Sensor Type:
Third party (2 to 20V).

Sensor Use:
Monitor voltage.

Table E-10 lists the points for Sensor Voltage versus input Voltage to A/D. Fig. E-10 shows the graph of these points.

Table E-10. Sensor Voltage Versus Input Voltage To A/D.