Venting installation, Preinstallation preparation – FMI BVC-50Y User Manual

Page 12

Advertising
background image

www.fmiproducts.com

122280-01E

12

VEntInG InStaLLatIOn

A FMI PRODUCTS, LLC or an 8" B-type vent-

ing system must be connected to appliance for

venting to the outside of building. Transition

pipe model BTC-8 is required for use with

B-type venting.
Standing codes requirements concerning

vent installations may vary within your state,

province or local codes jurisdiction. Therefore,

it is recommended that you check with your

local building codes for specific requirements

or in absence of local codes, follow Section

7.0 of the current National Fuel Gas Code

ANSI Z223.1/NFPA 54.
This gas appliance must be vented to the

outdoors only and may not be terminated into

an attic space or into a chimney flue servicing

a solid-fuel burning appliance.

Vent terminations must be located in ac-

cordance with height and proximity rules of

NFPA No. 54. These rules apply to vents at

12" diameter or less and require a minimum

height in accordance with the roof pitch and a

minimum of 8 ft. distance from a vertical wall

or obstruction (see Figure 11).

WARNING: This appliance

must be properly connected

to a system and must not be

connected to a chimney flue

servicing a separate solid fuel

burning appliance.

Lowest

Discharge

Opening

Listed

Vent Cap

8 Ft. Min.

Roof Pitch x/12

Listed Clearance

12

x

Listed

Gas

Vent

H (Min)

Height

From Roof

Figure 11 - Typical Terminations

Roof Pitch

H (Min.)

Feet

Meter

Flat to 6/12

1.0

0.30

6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

1

1

/

2

"

(3.8 cm)

Max.

3" (7.6 cm)

Max.

6" (15.2 cm)

Max.

9"

(22.9 cm)

12"

(30.5 cm)

Outer
Surround

Combustible

Material May

Be Used

TOP VIEW

SAFE

ZONE

Perpendicular
Wall

33°

Figure 10 - Side Clearances - Top View (Cross Section)

PREInStaLLatIOn PREPaRatIOn

Continued