J. T. Eaton Liquid-Cooled Drives LCX9000 User Manual

Page 113

Advertising
background image

LCX9000 Liquid-Cooled Drives User Manual

MN04005001E

For more information visit: www.EatonElectrical.com

A-3

January 2007

Table A-1: Fault Codes (Continued)

Programmable.

“A” faults only.

Fault
Code Fault

Possible Cause

Solution

29

Thermistor fault

The thermistor input of option board
has detected increase of the motor
temperature.

Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option
board is not in use, it has to be short
circuited)

31

IGBT temperature
(hardware)

IGBT Inverter Bridge
overtemperature protection has
detected too high a short term
overload current.

Check loading.
Check motor size.

34

CAN bus
communication

Sent message not acknowledged.

Ensure that there is another device

on the bus with the same
configuration.

36

Control unit

Control Unit can not control Power
Unit and vice versa.

Change control unit.

37

Device change
(same type)

• option board or control unit

changed.

• same type of board or same

power rating of drive

Reset
Note: No fault time data record!

38

Device added
(same type)

• option board or drive added.
• drive of same power rating or

same type of board added

Reset
Note: No fault time data record!

39

Device removed

• option board removed
• drive removed

Reset
Note: No fault time data record!

40

Device unknown

Unknown option board or drive.

Contact your Cutler-Hammer

distributor.

41

IGBT temperature

IGBT Inverter Bridge
overtemperature protection has
detected too high a short term
overload current.

Check loading.
Check motor size.

42

Brake resistor
overtemperature

Brake resistor overtemperature
protection has detected too heavy
braking.

Set the deceleration time longer.
Use external brake resistor.

43

Encoder fault

Note: the exceptional fault data
record, see Page 5-12. Additional
codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are
missing
4 = Encoder reversed

Check encoder channel connections.
Check the encoder board.

44

Device changed
(different type)

• option board or control unit

changed

• option board of different type or

different power rating of drive

Reset.
Note: No Fault Time Data Record is
made.
Note: Application parameter values
restored to default.

Advertising