J. T. Eaton Liquid-Cooled Drives LCX9000 User Manual

Page 37

Advertising
background image

LCX9000 Liquid-Cooled Drives User Manual

MN04005001E

For more information visit: www.EatonElectrical.com

2-15

January 2007

Pressure Losses

Table 2-11: Pressure Losses — CH6x

Figure 2-15: Pressure Loss — CH6x

CH6x with standard 1.5m hoses and optional fast connectors TEMA

Volume
Flow
Rate
(GPM)

Pressure
Loss
TEMA
Inflow
(psi)

Pressure
Loss
Inflow
Hose (psi)

Pressure
Loss
Element
(psi)

Pressure
Loss
Outflow
Hose (psi)

Pressure
Loss TEMA
Outflow
(psi)

Pressure Loss
Total Inflow
Hose, Element
and Outflow
Hose (psi)

Pressure Loss Total
TEMA, Inflow and
Outflow Hoses and
Element (psi)

10.6

8.56

4.35

4.06

4.06

7.40

12.62

28.43

7.9

4.35

2.47

2.32

2.32

3.63

7.12

15.08

5.3

1.45

1.31

1.16

1.02

1.31

3.48

6.24

4.5

0.87

1.02

0.87

0.44

1.02

2.32

4.21

2.5

5.0

7.5

10.0

12.5

0.00

5.00

10.00

15.00

20.00

25.00

30.00

Pressure Loss, psi

Vo

lu

me

F

lo

w

R

a

te

, GPM

Pressure loss; TEMA,
inflow (SET-SEL) (bar)

Pressure loss; inflow
hose (SEL-SEE) (bar)

Pressure loss;
element (SEE-PEJ)

Pressure loss; outflow
hose: (PEJ-PLJ) (bar)

Pressure loss; TEMA,
outflow (PLJ-PTJ)(bar)

Pressure loss total
(inflow hose, element
and outflow hose)

Pressure loss total
(TEMA, inflow and
outflow hoses and
element)

Legend

Advertising