LCX9000 Liquid-Cooled Drives User Manual

MN04005001E

For more information visit: www.EatonElectrical.com

2-11

January 2007

Figure 2-11: Example PI-Diagram of Cooling System and Connections

Table 2-7 shows the specifications related to the cooling agent and its circulation. Also see
Table 1-4, Technical Information on Page 1-9.

Table 2-7: Information About Cooling Agent and Its Circulation

A = 100% water; B = Water/Glycol mixture 80:20; C = Water/Glycol mixture (60:40)

Definitions: Min. liquid flow = Minimum flow rate to ensure of total venting of the cooling

element

Nom. liquid flow = Flow rate while running the drive at I

th

Max. liquid flow = If flow rate exceeds max. liquid flow, risk of cooling element
erosion increases

Note: Unless minimum liquid flow rate is ensured, air pockets may develop in the cooling

elements.

Chassis

Min. Liquid Flow
per Element (Drive)
in GPM

Nom. Liquid Flow per
Element (Drive)
in GPM

Max. Liquid Flow
per Element (Drive)
in GPM

A

A

B

C

A

CH3

.8 (.8)

1.3 (1.3)

1.4 (1.4)

1.5 (1.5)

5.3 (5.3)

CH4

2.1 (2.1)

2.6 (2.6)

2.9 (2.9)

3.2 (3.2)

5.3 (5.3)

CH5

2.6 (2.6)

4.0 (4.0)

4.2 (4.2)

4.5 (4.5)

10.6 (10.6)

CH61

5.3 (5.3)

6.6 (6.6)

7.1 (7.1)

7.7 (7.7)

10.6 (10.6)

CH62

5.3 (5.3)

6.6 (6.6)

7.1 (7.1)

7.7 (7.7)

10.6 (10.6)

CH63

5.3 (10.6)

6.6 (13.2)

7.1 (14.3)

7.7 (15.3)

10.6 (21.1)

CH64

5.3 (15.9)

6.6 (19.8)

7.1 (21.1)

7.7 (22.7)

10.6 (31.7)

CH72

5.3 (5.3)

9.2 (9.2)

9.8 (9.8)

10.6 (10.6)

10.6 (10.6)

CH74

5.3 (15.9)

9.2 (26.4)

9.8 (29.6)

10.3 (32.0)

10.6 (31.7)

FV01

DN32

LS01

DN32

IE

Cooling Water Inlet

Cooling Water Outlet

P01

PA01

Drives

W01

TE
41

PE
41

TI

PE
42

PI

LT
40

LE
40