LCX9000 Liquid-Cooled Drives User Manual

4-6

For more information visit: www.EatonElectrical.com

MN04005001E

January 2007

Control Cables

The control cables should be at least 20 AWG (.5 mm

2

) screened multicore cables, see Table

3-1. The maximum terminal wire size is 14 AWG (2.5 mm

2

) for the relay terminals and 16

AWG (1.5 mm

2

) for other terminals.

Galvanic Isolation Barriers

The control connections are isolated from the mains potential and the GND terminals are
permanently connected to ground. See Figure 4-9.

The digital inputs are galvanically isolated from the I/O ground. The relay outputs are
additionally double-isolated from each other at 300V AC (EN-50178).

Figure 4-9: Galvanic Isolation Barriers

RO1/1

Control I/O
Ground

Digital Input
Group A

Digital Input
Group A

Analog
Output

Digital
Output

RO1/2
RO1/3

RO2/1
RO2/2
RO2/3

TI1+

TI1–

AI1

+10Vref

+24V

GND

GND

AI2+

AI2-

DIN1...
DIN3
CMA

DIN4...
DIN6
CMB

AO1+

AO2-

DO1

Control

Panel

Gate Drivers

Control

Board

Power

Board

U

V

W

L1

L2

L3