LCX9000 Liquid-Cooled Drives User Manual

3-4

For more information visit: www.EatonElectrical.com

MN04005001E

January 2007

Table 3-3: Cable Sizes 525 – 690V

Due to insufficient number of terminal bolt connections for required number of cables, the cabinet must be equipped with an
external flexible cable connection block at both mains and motor ends if stiff cable type is used. See also Page 3-7, Step 5.

Number of bolt connections = 4.

Three grounding terminals per mounting plate, see Page 3-10.

See the tightening torques of bolts in Table 3-4.

Table 3-4: Tightening Torques of Bolts

We recommend a low-impedance grounding of the motor cable shield for better
performance.

Because of several possible cable installations and environmental conditions, it is very
important to consider local regulations and the IEC/EN standards.

Chassis

Catalog
Number

I

th

Mains and
Motor Cable
Cu (mm

2

)

Terminal Cable Size

Max. Number of
Cables/Bolt Size

Main Terminal
(mm

2

), Max.

Ground Terminal
(mm

2

)

CH61

LCX170A0-5

170 3x95+50

185 Cu/Al

25 – 95

2/M12

LCX208A0-5

208 3x150+70

185 Cu/Al

25 – 95

2/M12

LCX261A0-5

261 3x185+95

185 Cu/Al 2

25 – 95

2/M12

CH62/72 LCX325A0-5

325 2x(3x95+50)

25 – 185

4/M12

LCX385A0-5

385 2x(3x120+70)

25 – 185

4/M12

LCX416A0-5

416 2x(3x150+70)

25 – 185

4/M12

LCX460A0-5

460 2x(3x185+95)

25 – 185

4/M12

LCX502A0-5

502 2x(3x185+95)

25 – 185

4/M12

CH63

LCX590A0-5

590 3x(3x150+70)

8/M12

LCX650A0-5

650 3x(3x150+70)

8/M12

LCX750A0-5

750 3x(3x185+95)

8/M12

CH74

LCX820A0-5

820 4x(3x150+70)

4/M12

LCX920A0-5

920 4x(3x185+95)

4/M12

LCXH10A0-5

1030 4x(3x185+95)

4/M12

LCXH11A0-5

1180 5x(3x185+95)

4/M12

LCXH13A0-5

1300 5x(3x185+95)

4/M12

LCXH15A0-5

1500 6x(3x185+95)

4/M12

Bolt

Tightening Torque in in-lb
(Nm)

Max. Inward Thread Length
(mm)

M8

177 (20)

10

M10

354 (40)

22

M12

620 (70)

22