Installation Space

Enough free space must be left above and below the drive to ensure practical and
appropriate electrical and cooling connections. The minimum dimensions are given in the
table below. No space is required to the left and right of the drive.

Figure 3-2: Installation Space

A

B

Distance to the cable connection block. Additional
space must be reserved for ferrite rings, if used.
See Page 3-1.

Chassis

Approximate Dimensions
in Inches (mm)

A

B

CH3

3.94 (100)

5.91 (150)

CH4

3.94 (100)

7.87 (200)

CH5

3.94 (100)

7.87 (200)

CH61

3.94 (100)

11.81 (300)

CH62

3.94 (100)

15.75 (400)

CH63

7.87 (200)

15.75 (400)

CH64

7.87 (200)

19.69 (500)

CH72

7.87 (200)

15.75 (400)

CH74

7.87 (200)

19.69 (500)