LCX9000 Liquid-Cooled Drives User Manual

1-10

For more information visit: www.EatonElectrical.com

MN04005001E

January 2007

Table 1-4: Technical Information (Continued)

Description

Specification

EMC

Immunity

Fulfils all EMC immunity requirements

Emissions

EMC level N; EMC level T for IT networks

Safety

Approvals

EN50178, EN60204-1, CE, UL, CUL, FI, GOST R,
(see unit nameplate for more detailed approvals)

Safe disable board

The drive is equipped with OPTAF board for prevention of torque on
motor shaft. Standards: EN954-1, cat. 3 (hardware disable); BGIA
(Safe Disable Function).

Control connections (apply to boards OPT-A1, OPT-A2 and OPT-A3)

Analog input voltage

0 to +10V, R

i

= 200kΩ, (-10V to +10V joystick control)

Resolution 0.1%, accuracy ±1%

Analog input current

0(4) – 20 mA, R

i

= 250Ω differential

Digital inputs (6)

Positive or negative logic; 18 – 24V DC

Auxiliary voltage

+24V, ±10%, max volt. ripple <100 mVrms; max. 250 mA
Dimensioning: max. 1000 mA/control box
1A external fuse required (no internal short-circuit protection on the
control board)

Output reference voltage

+10V, +3%, max. load 10 mA

Analog output

0(4) – 20 mA; R

L

max. 500Ω; Resolution 10 bit; Accuracy ±2%

Digital outputs

Open collector output, 50 mA/48V

Relay outputs

2 programmable change-over relay outputs
Switching capacity: 24V DC/8A, 250V AC/8A, 125V DC/.4A
Min. switching load: 5V/10 mA

Protections

Overvoltage trip limit
Undervoltage trip limit

480V: 911V; 575V: 1200V (all VDC)
480V: 333V; 575V: 461V (all VDC)

Ground fault protection

In case of ground fault in motor or motor cable, only the drive is
protected

Mains supervision

Trips if any of the input phases is missing

Motor phase supervision

Trips if any of the output phases is missing

Unit overtemperature protection Alarm limit: 149°F (65°C) (heatsink); 158°F (70°C) (circuit boards)

Trip limit: 158°F (70°C) (heatsink); 185°F (85°C) (circuit boards)

Overcurrent protection

Yes

Motor overload protection

Yes

Motor stall protection

Yes

Motor underload protection

Yes

Short-circuit protection of +24V
and +10V reference voltages

Yes

Liquid Cooling

Allowed cooling agents

Drinking water (see specification on Page 2-7)
Water-glycol mixture
See derating specifications on Page 2-19

Volume

See Page 2-11.

Temperature of cooling agent

32 – 86°F (0 – 30°C) (I

th

)(input); 86 – 149°F (30 – 65°C): derating

required, see Page 2-19.
Max. temperature rise during circulation max. 41°F (5°C)
No condensation allowed. See Pages 2-13.

Cooling agent flow rates

See Table 2-7.

System max. working pressure

87 psi

System max. peak pressure

580 psi

Pressure loss (at nominal flow)

Varies according to size. See Table 2-10.