Cooling

Instead of using air for cooling, Cutler-Hammer Liquid-Cooled drives are cooled with liquid.
The liquid circulation of the drive is usually connected to a heat-exchanger (liquid-liquid/
liquid-air) which cools down the liquid circulating in the cooling elements of the drive. The
cooling agents acceptable for use are drinking water, demineralized water or a mixture
(60/40) of water and glycol. In a closed circulation system, the values in Table 2-3 are
recommended reference values. To avoid electrochemical corrosion, Eaton recommends
adding an inhibitor (e.g. Ferrolix 332/Henkel or Cortec VpCI-649) in the cooling agent.

Note: If no heat-exchanger is used, actions must be taken to avoid electrochemical corrosion.

Specifically no brass or copper elements may be used in the liquid circulation of the drive.

Drinking Water Specification

Table 2-3 provides general guidelines for water quality.

Note: 1 mg/L = 1 ppm.

Table 2-3: Drinking Water Chemical Specification

Table 2-4: Drinking Water Quality
Recommendations — Maximum Values

No aggressive water allowed.

To avoid corrosion of piping, the sulphate content must not
exceed 150 mg/L.

Quality

Unit

Value

Quality

Unit

Value

Acrylamide

µg/L

0.10

Mercury

µg/L

1.0

Antimony

µg/L

5.0

Nickel

µg/L

20

Arsenic

µg/L

10

Nitrate [NO

3

]

mg/L

50

Benzene

µg/L

1.0

Nitrate-Nitrogen [NO

3

-N]

mg/L

11.0

Benzopyrene

µg/L

0.010

Nitrite [NO

2

]

mg/L

0.5

Boron

mg/L

1.0

Nitrite-Nitrogen [NO

2

-N]

mg/L

0.15

Bromate

µg/L

10

Bactericides

µg/L

0.10

Cadmium

µg/L

5.0

Bactericides, total

µg/L

0.50

Chromium

µg/L

50

Polynuclear aromatic
hydrocarbons

µg/L

0.10

Copper

mg/L

2.0

Selenium

µg/L

10

Cyanides

µg/L

50

Tetrachloroethylene and
trichloroethylene total

µg/L

10

1,2-Dichloroethane

µg/L

3.0

Trihalomethanes total

µg/L

100

Epichlorohydrin

µg/L

0.10

Vinyl chloride

µg/L

0.50

Fluoride

mg/L

1.5

Chlorophenols total

µg/L

10

Lead

µg/L

10

Quality

Unit

Max.
Value

Aluminum

µg/L

200

Ammonium [NH

2

]

mg/L

0.50

Ammonium [NH

2

-N]

mg/L

0.40

Chloride

mg/L

<100

Manganese

µg/L

50

Iron

µg/L

<0.5

Sulphate

ᕃᕄ

mg/L

250

Sodium

mg/L

200

Oxidizability [COD

Mn

-O

2

]

mg/L

5.0

Advertising