Quick Start (P001 to P007)

P001 Operation

Sets the type of measurement required for the application.

P002 Material

Specifies material type. If the material presents a flat surface perpendicular to the

transducer beam, select liquid.

P003 Maximum Process Speed

Determines level change reaction speed.

Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.

Values

0

Out-of-service

1

Level – how full the vessel is (Point 1 and/or 2 only)

2

Space – how empty the vessel is (Point 1 and/or 2 only)

3

*

Distance – distance from transducer to material (Point 1 and/
or 2 only)

Values

1

*

Liquid or flat surface

2

Solid or angled surface

Alters

•

P830 TVT Type

Values

1

Slow (0.1 m/min)

2

*

Medium (1 m/min)

3

Fast (10 m/min)

4

Surge (1.7 m/sec)

5

Immediate (17 m/sec)

Alters

•

P070 Failsafe Timer

•

P700 Max Fill Rate

•

P701 Max Empty Rate

•

P702 Filling Indicator

•

P703 Emptying Indicator

•

P704 Rate Filter

•

P710 Fuzz Filter

•

P713 Echo Lock Window

•

P727 Scan Delay

•

P841 Long Shot Number

Related

•

Failsafe (P070 to P072)

•

Rate (P700 to P708)

•

Measurement Verification (P710 to P713)

•

Transducer Scanning (P726 to P729)

•

P905 Transmit Pulse