P334 Auto Record ON Setpoint

Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the

boundaries for Auto Profile Records to be saved.

P335 Auto Record OFF Setpoint

Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the

boundaries for Auto Profile Records to be saved.

P336 Auto Record Filling / Emptying

Use this feature to restrict Auto Profile Records from being saved unless the level is

rising, falling or either.

If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.

P337 Auto Record LOE Time

Limits Auto Profile Records from being saved unless extended LOE occurs.

If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.

Values

Range: -999 to 9999

Related

P335 Auto Record OFF Setpoint

P336 Auto Record Filling / Emptying

P337 Auto Record LOE Time

Values

Range: -999 to 9999

Related

P334 Auto Record ON Setpoint

P336 Auto Record Filling / Emptying

P337 Auto Record LOE Time

Values

0

*

Auto Profile Record on filling or emptying

1

Auto Profile Record on filling only

2

Auto Profile Record on emptying only

Related

P334 Auto Record ON Setpoint

P335 Auto Record OFF Setpoint

P337 Auto Record LOE Time

P702 Filling Indicator

P703 Emptying Indicator

Values

Range: 0.0 to 9999 (seconds)
Preset: 0.0

Related

P334 Auto Record ON Setpoint

P335 Auto Record OFF Setpoint

P336 Auto Record Filling / Emptying