Custom Relays (P111 to P113)

P111 Relay Control Function

Sets the control algorithm used to trip the relay.
When accessed, the Parameter Type display changes to the Relay symbol and the Index
display changes to the Relay Number (corresponding to the SITRANS LU01 terminals).

Use zero 0 (preset) to disable control of the indexed relay.

To enter a relay designation:

1.

Press

to display the Auxiliary Function symbol,

2.

Press

or

to scroll access the desired relay designation and...

3.

Press .

Refer to Point Alarm and Status section in SmartLinx instruction manuals for more
information.

Primary Index

Relay

Values

See chart on next page

Altered by

P100 Preset Applications

Note:

All relay ON/OFF points must be referenced from Empty (P006), regardless

of Operation Mode selection (POO1).

Function

Designation

Operation

Level

LL, L, H, or HH

Similar to Standard Alarms but with Relay ON/OFF Setpoints

In Bounds

b1 or b2

1

1.

The relay designation is not displayed but is included in the data message.

Alarms when level is between the Relay ON/OFF Setpoints

Out of Bounds b1 or b2

1

Alarms when level is not between the Relay ON/OFF Set-
points

Rate

r1 or r2

1

Level rate of change alarm with Relay ON/OFF Setpoints

Temperature

Not applicable

Alarm is activated by independent Relay ON/OFF Setpoints

LOE

Not applicable

Relay de-energizes in the event of Failsafe timer (P700) expiry

Cable fault

Not applicable

Relay de-energizes under transducer short or opened condi-
tion

Pump

Not applicable

With independent Relay ON/OFF Setpoints

Note:

When the Relay Function is altered, affected Alarm Parameters (P101 to

P104) display "ch" (changed) when accessed. Use the Relay ON/OFF Setpoints
(P112/P113) instead.