P052 tank dimension a, P053 tank dimension l, Universal volume calculation – Siemens sitrans LU01 User Manual

Page 40

Advertising
background image

Page 34

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

P052 Tank Dimension A

Dimension A as used in P050 Tank Shape.

Enter one of the following:

height of the tank bottom if P050 = 2, 3, 4, or 5

or

length of one end section of the tank if P050 = 7, in Units (P005)

P053 Tank Dimension L

Dimension L as used in P050 Tank Shape.

Enter the following:

tank length (excluding both end sections) if P050 = 7

Universal Volume Calculation

P054 and P055 use secondary indices.To access a secondary index:

1.

Press DISPLAY

to activate primary index. The

icon appears under the index

field.

2.

Enter the values to set the breakpoints.

P054 Level Breakpoints (Universal Volume Calculation)

When the tank shape is too complex for any of the preconfigured shapes, you can specify

the volume based on segments.

Enter the following:

up to 32 level breakpoints (where volume is known) if P050 = 9 or 10

Values

Range: 0.0 to 9999
Preset: 0.000

Related

P050 Tank Shape

Values

Range: 0.0 to 9999
Preset: 0.000

Related

P050 Tank Shape

Primary Index

Breakpoint

Values

Range: 0.0 to 9999

Related

P055 Volume Breakpoints

Advertising