SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
P052 Tank Dimension A
Dimension A as used in P050 Tank Shape.
Enter one of the following:
•
height of the tank bottom if P050 = 2, 3, 4, or 5
or
•
length of one end section of the tank if P050 = 7, in Units (P005)
P053 Tank Dimension L
Dimension L as used in P050 Tank Shape.
Enter the following:
•
tank length (excluding both end sections) if P050 = 7
Universal Volume Calculation
P054 and P055 use secondary indices.To access a secondary index:
1.
Press DISPLAY
to activate primary index. The
icon appears under the index
field.
2.
Enter the values to set the breakpoints.
P054 Level Breakpoints (Universal Volume Calculation)
When the tank shape is too complex for any of the preconfigured shapes, you can specify
the volume based on segments.
Enter the following:
•
up to 32 level breakpoints (where volume is known) if P050 = 9 or 10
Values
Range: 0.0 to 9999
Preset: 0.000
Related
•
P050 Tank Shape
Values
Range: 0.0 to 9999
Preset: 0.000
Related
•
P050 Tank Shape
Primary Index
Breakpoint
Values
Range: 0.0 to 9999
Related
•
P055 Volume Breakpoints