P071 failsafe material level – Siemens sitrans LU01 User Manual

Page 44

Advertising
background image

Page 38

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

If the timer expires (before a valid measurement is made), the SITRANS LU01 advances to
the Failsafe Material Level (P071) as restricted by Failsafe Advance (P072).

When a valid measurement is made after the timer expires, the SITRANS LU01 advances
to the new material level (if changed), as restricted by Failsafe Advance (P072) and the
timer resets.

If the timer expires due to a measurement difficulty, LOE flashes in the Reading display.

Once activated, the Failsafe State initiates the following:

1.

The material level is reported based on P071 Failsafe Material Level.
• The unit responds to the new level as programmed (control and alarm relays

activate as defined by the programming).

• Individual relays can have independent failsafe responses. See

P129 Relay

Failsafe.

2.

The appropriate error is displayed:

• LOE for loss of echo from the transducer
• Short for a shorted transducer cable
• Open for a cut transducer cable or a defective transducer
• Error for all other problems including reversed Ultrasonic/Temperature

transducer terminal connections or wrong Transducer (P004) entered.

When modifying the preset value, set it short enough to protect the process but long
enough to avoid false alarms. Only use No Delay (0.0 Minutes) for testing.

P071 Failsafe Material Level

The material level reported when a Failsafe State is initiated.

Select the Failsafe Material Level based upon the relay operation required during failsafe
operation.

Selecting HI, LO, or HOLd

1.

Press FUNCTION

to display the Auxiliary Function symbol.

2.

Press ARROWS

to scroll to the desired option.

3.

Press ENTER

to set the value.

Values

Range: -999 to

9999

Value in units or % (-50% to 150% of span)

HI

Level goes to maximum span

LO

Level goes to 0 span (Empty)

HOLd

*

Level remains at last reading

Related

P001 Operation

P006 Empty

P007 Span

P111 Relay Control Function

P112 Relay ON Setpoint

P113 relay OFF Setpoint

P129 Relay Failsafe

Advertising