P702 filling indicator, P703 emptying indicator, P704 rate filter – Siemens sitrans LU01 User Manual
Page 65
7ML19985BE02
SITRANS LU01 – INSTRUCTION MANUAL
Page 59
m
mmmm
Pa
ra
m
e
te
rs
P702 Filling Indicator
The fill rate required to activate the LCD Filling indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Fill Rate (P700).
P703 Emptying Indicator
The empty rate required to activate the LCD Emptying indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Empty Rate (P701).
P704 Rate Filter
Damps Rate Value (P707) fluctuations.
Enter the time or distance interval over which the Rate Value is to be calculated before
the display updates.
This is automatically altered along with Maximum Process Speed (P003).
This value automatically alters the Rate Update Time (P705) and / or Rate Update
Distance (P706). Alternatively, these parameter values may be altered independently.
Values
Range: -999 to 9999
Altered by
•
P003 Maximum Process Speed
Related
•
P005 Units
•
P007 Span
•
P700 Max Fill Rate
Values
Range: -999 to 9999
Altered by
•
P003 Maximum Process Speed
Related
•
P005 Units
•
P007 Span
•
P701 Max Empty Rate
Values
0
Rate display not required
Filtered Output
1
Continuously filtered and updated
Interval Output
2
1 minute or 50 mm (2 in)
3
5 minutes or 100 mm (3.9 in)
4
10 minutes or 300 mm (11.8 in)
5
10 minutes or 1000 mm (39.4 in)
Alters
•
P707 Rate Value
Altered by
•
P003 Maximum Process Speed
Related
•
P705 Rate Update Time/ P706 Rate Update Distance