Advanced tvt adjustment (p830 to p835), P825 echo marker trigger, P830 tvt type – Siemens sitrans LU01 User Manual

Page 81

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 75

m

mmmm

Pa
ra

m

e

te

rs

Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates
slightly, though the monitored surface is still. Enter the amount (in ms) of long shot Echo
Profile smoothing required. When a value is keyed in, the nearest acceptable value is
entered.

P825 Echo Marker Trigger

The point on the primary echo on which the measured value is based.

Use this feature if the reported material level fluctuates slightly, due to a variable rise in
the leading edge of the true echo on the Echo Profile.

Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo.
This value is preset to 90% when P002=1 (Liquid) or 50% when P002=2 (Solid).

Advanced TVT Adjustment (P830 to P835)

Advanced TVT control applies to long shots only.

P830 TVT Type

Selects the TVT Curve used.

Values

Range: 5 to 95%
Preset: 90% when P002=1 (Liquid) or 50% when P002=2 (Solid)

Related

•

P817 Profile Pointer Time

•

P818 Profile Pointer Distance

•

P819 Profile Pointer Amplitude

•

P820 Algorithm

•

P821 Spike Filter

•

P822 Narrow Echo Filter

•

P823 Reform Echo

Note:

The following parameters are for authorized Siemens Milltronics Service

personnel or technicians familiar with Siemens Milltronics echo processing
techniques.

Values

1

TVT Short Curved

2

TVT Short Flat

3

TVT Long Flat

4

TVT Long Smooth Front

5

TVT Long Smooth

6

TVT Slopes

Altered By

•

P002 Material

Related

•

P805 Echo Confidence

•

P835 TVT Slope Min