P731 Auxiliary Reading Key

Enter the Parameter Number whose value is to be displayed in the Auxiliary Reading field

is pressed in the RUN mode. See the

Keypad section on page 24 for RUN mode

auxiliary readings.

P732 Display Delay

Adjusts the Point Number display scroll speed.

Use this feature to adjust the delay before the display advances to the next Point Number.
Display scrolling is independent from transducer scanning.

P733 Scroll Access

Use this feature to select the parameter scroll access option desired.

Press READING

and

to tag / untag any accessed parameter.

is displayed to

indicate the parameter accessed is tagged.

Values

Range: 000 to 999
Preset: Material Reading, P921

Values

Range: 0.5 to 10
Preset: 1.5 seconds

Related

P001 Operation

Values

0

Off

to scroll to all parameters (P001 to P999)

1

* Smart

for Quick Start, altered, and tagged parameters

2

Tagged

to scroll to operator tagged parameters only

Note:

Quick Start parameters (P001 – P007) and those changed from factory

default settings cannot be untagged.