Description of the PROFINET Configuration File

290

Commissioning PC Stations - Manual and Quick Start

Release 5/2005

C79000- G8976 - C156 - 07

The InitiateTimeout Parameter

This parameter is specified in section [<connectionname>].

The connection name contains the IP address from the iMap project engineering
(network view) and the PROFInet device name configured in iMap.

Parameter

Meaning

Syntax

[192.11.2.34|S7-300 Station (1)]

InitiateTimeout = 15000

Purpose

If a connection establishment job cannot be
processed within the InitiateTimeout time, the
connection is reset and the job is started again.

Particularly when establishing connections using
DCOM from Microsoft, wait times of several
minutes can occur if the partner does not exist or if
the connection has broken down. During this time,
further actions on the connection are blocked
because the access is synchronous. This wait time
can be reduced with this parameter.

Default

10000

Possible Values

milliseconds