6

Using the CP 1616 as a PROFINET IO Controller/Device

76

Commissioning PC Stations - Manual and Quick Start

Release 5/2005

C79000-G8976-C156-07

Follow the steps outlined below

4.

In the “PROFINET” tab, you can set the mode of the CP 1616.

Select the options “PROFINET IO Controller” and “Enable PROFINET IO device operation”.

Then confirm your entries with OK.

5.

Configure a SIMATIC PC station in HW Config and place a CP 1612 in it.

Note

In the “Properties - Ethernet Interface CP 1612” dialog, select a different network than used for
the configuration of the CP 1616, or configure a new network.

6.

Select the CP 1612 and then select Edit

"

Object Properties.

7.

You can set the mode of the CP 1612 in the “PROFINET” tab.

Select the “PROFINET IO Controller” option.

Then confirm your entries with OK.

8.

Select the CP 1612 and then select the menu command Insert

"

PROFINET IO System.

9.

In the hardware catalog (PROFINET IO

"

I/O

"

SIMATIC PC CP

),

select the CP 1616 and

position it in the network (PROFINET IO System).

This configures the CP 1616 is as a device in the network.

10.

Select the CP 1616 and select Edit

"

Object Properties.

11.

Enter the device name in the “Device name” input box.

Make sure that the device name is identical to the device name of the CP 1616 in the PC