Description of the PROFINET Configuration File

291

Commissioning PC Stations - Manual and Quick Start
Release 5/2005

C79000- G8976 - C156 - 07

The Timeout Parameter

This parameter is specified in section [<connectionname>].

The connection name contains the IP address from the iMap project engineering
(network view) and the PROFInet device name configured in iMap.

Parameter

Meaning

Syntax

[192.11.2.34|S7-300 Station (1)]

Timeout = 15000

Purpose

The “Timeout” parameter is an error monitoring
time. If a pending job cannot be processed within
this monitoring time, the job is acknowledged with
an error.

Default

15000

Possible Values

milliseconds

The QualityOfStateValue Parameter

This parameter is specified in section [<connectionname>].

The connection name contains the IP address from the iMap project engineering
(network view) and the PROFInet device name configured in iMap.

Parameter

Meaning

Syntax

[192.11.2.34|S7-300 Station (1)]

QualityOfStateValue = 100

Purpose

The required QualityofServiceValue is used to
restrict the frequency of transmission of data on a
partner device. It describes the required update
quality of the data. Process value on the partner
device are updated at this sampling rate.

Default

100 (the cycle time of the PROFInet OPC Server)

Possible Values

milliseconds