3 removing piano jacks, 4 mechanical considerations, 1 positioning the liebert xdc – Liebert Extreme Density Chiller XDC User Manual

Page 10: Figure 5 dimensional data, Table 1 liebert xdc dimensions, weight, Removing piano jacks, Mechanical considerations, Positioning the liebert xdc, Figure 5, Dimensional data

Advertising
background image

Product Description

4

1.3.3 Removing Piano Jacks

Once the unit has been moved to the installation location, Emerson Network Power recommends

using the following method to remove the piano jacks.
1. Lower the unit as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Remove all cushioning material that might have been used to protect the unit panels from the

strapping and/or the piano jacks.

4. Use a pry bar or similar device on one side of the unit, lift unit just enough to allow for the

removal of the piano jack.

5. Repeat the previous step to remove the piano jack on the opposite side.
6. Remove the plastic bag.

1.4

Mechanical Considerations

1.4.1 Positioning the Liebert XDC

Install the Liebert XDC according to the site specific documentation and secure the unit to the floor.
The Liebert XDC can be installed near a wall or another Liebert XDC. However, there must be at

least 3 feet (92cm) clearance in front of the Liebert XDC as service access for components in the unit.

Figure 5

Dimensional data

NOTE
During installation of the Liebert XDC, the top, bottom, front and left side of the unit

must be accessible.

Table 1

Liebert XDC dimensions, weight

Air Cooled

Model

Dimensional Data, inches (mm)

Shipping Weight, lb (kg)

50/60Hz

A

B *

C

D

E

Domestic

Export

XDC160

74 (1880)

34 (864)

33-1/8 (841)

33 (838)

72 (1829)

1945 (882)

2093 (949)

* Dimension does not include the bezel of the disconnect switch.

C

D

B

Overall

5"

(127mm)

17"

(432mm)

1"

(25.4mm)

2"

(51mm)

78"

1981mm

A

Overall

Shaded areas indicate a
recommended clearance
of 34" (864mm) for
component access.

D

Unit

Base

E

Unit Base

Unit Dimensional Data

Floor Cutout Dimensions

DPN000768
Page 2, Rev. 6

Recommended
Minimum Hot Gas
Supply & Liquid Return
Piping Opening