Specifications

55

Table 26

Floor stand specifications—water-cooled Liebert XDC

Models - 60 Hz

XDC160 Water Floor Stand - 60Hz

Entering Fluid Temp °F (C)

65 (18)

70 (21)

75 (24)

85 (29)

95 (35)

Performance Data

Cooling capacity, tons (kW)

46.1(162.3)

46.1(162.3)

46.1(162.3)

46.1(162.3)

44.5 (156.5)

Flow, GPM

50

58

70

110

142

Pressure Drop, psi (Ft Water)

2.7 (6.2)

4.9 (11.3)

5.4 (12.5)

20.7 (47.8)

27.3 (63.1)

Heat Rejection Equipment

Water regulating valve size

1"

1"

1"

1"

1"

Piping Connections

Water / glycol supply and return lines

2-1/8"

2-1/8"

2-1/8"

2-1/8"

2-1/8"

Table 27

Floor stand specifications—Liebert XDC with 40% propylene glycol

Models - 60 Hz

XDC160 Glycol Floor Stand - 60Hz - 40% PG

Outside Ambient °F (°C)

95 (35)

100 (38)

105 (41)

Entering Fluid Temp °F (°C)

110 (43)

110 (43)

110 (43)

Performance Data

Cooling capacity, tons (kW)

42.5 (149.4)

Total Heat Rejection, (kW)

192.6

Flow, GPM

206

Pressure Drop, psi (ft water)

37.2 (85.9)

Heat Rejection Equipment

Drycooler

DNT 940A

2 x DNT 880A*

Drycooler Pressure Drop, psi (ft water)

6.7 (15.5)

2.9 (6.6)

Glycol pump package - 10hp

9A31258G3

Pump Control Package - 208V

9A34606G47

Pump Control Package - 460V

9A32114G4

Pump Total Head @ 204 GPM, ft water

145

Water regulating valve size

1-1/4"

Piping Connections

Water / glycol supply and return lines

2-5/8"

* When multiple drycoolers are used ensure flow is balanced.