Table 28 – Liebert Extreme Density Chiller XDC User Manual

Page 62

Advertising
background image

Specifications

56

Table 28

Floor stand specifications—Liebert XDC with 40% ethylene glycol

Models - 60 Hz

XDC160 Glycol Floor Stand - 60Hz - 40% EG

Outside Ambient °F (°C)

95 (35)

100 (38)

105 (41)

Entering Fluid Temp °F (°C)

110 (43)

110 (43)

110 (43)

Performance Data

Cooling capacity, tons (kW)

42.5 (149.4)

Total Heat Rejection, (kW)

192.6

Flow, GPM

204

Pressure Drop, psi (ft water)

35.9 (82.9)

Heat Rejection Equipment

Drycooler

DNT 940A

2 x DNT 880A*

Drycooler Pressure Drop, psi (ft water)

6.5 (15.1)

2.7 (6.3)

Glycol pump package - 10HP

9A31258G3

Pump Control Package - 208V

9A34606G47

Pump Control Package - 460V

9A32114G4

Pump Total Head @ 204 GPM, ft water

145

Water regulating valve size

1-1/4"

Piping Connections

Water / glycol supply and return lines

2-5/8"

* When multiple drycoolers are used ensure flow is balanced.