Piping and Filling with Refrigerant: R-134a and R-407c Circuits

27

Figure 27 General arrangement air cooled Liebert XDC Lee-Temp Control

Table 12

Recommended refrigerant line sizes, DX R-407c, OD copper

Liebert XDC 160

Equivalent

Length, ft., (m)

*Hot Gas Line,

in.

Liquid Line, in.

50 (15)

1-1/8

7/8

100 (30)

1-1/8

1-1/8

150 (45)

1-3/8

1-1/8

200 (60)

1-3/8

1-1/8

* Double risers are required when hot gas vertical rise is 15 feet or
more (see 2.6 - Install Double Discharge Risers).

Traps * every 25 ft.
(7.6m) of rise on hot
gas line only

Condenser Coil

Hot Gas/Discharge

Liquid/Return

Standard Piping
Assembly **

Rotalock
Valve **

1/4" (6.4mm)
Pressure Relief
Valve **

Sight Glass
Some Models
Have 2 Sight Glasses

Lee-Temp
Receiver

Check
Valve

Head Pressure
Control with
Integral Check
Valve

Liquid Return

from Condenser

Inverted Trap * on discharge
line to extend above base of
coil by a minimum of
7-1/2" (190mm)

Additional
Piping
Assembly **

DPN000937
Pg. 4, Rev 9

* * Components supplied by
Liebert and must be
field-installed.

* Components are not supplied by
Liebert but are recommended
for proper circuit operation and
maintenance.

Single XDC Circuit Shown

Field-Supplied Piping

Factory-Supplied Piping