5 high voltage connections, 1 connecting high-voltage cables, High voltage connections – Liebert Extreme Density Chiller XDC User Manual

Page 16: Connecting high-voltage cables, Warning, Caution

Advertising
background image

Product Description

10

1.5

High Voltage Connections

Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated

on the Liebert XDC’s rating plate.
Connect cables for high voltage supply to the electrical box in the Liebert XDC according to

Figures 5, 11 and 12 and make sure that the phases are correctly connected.

1.5.1 Connecting High-Voltage Cables

1. Turn the Liebert XDC’s primary disconnect switch to the Off position (see Figure 10). Open the

front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure

cover.

Figure 10 Front view of Liebert XDC and electrical enclosures

!

WARNING

Risk of electric shock. Can cause death or injury.
Disconnect all local and electric remote power supplies before working within.

!

CAUTION

Risk of sharp edges and heavy parts. May cause personal injury or equipment damage.
Wear gloves to prevent injury to hands.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.

NOTE
Before beginning to install the Liebert XDC, read all instructions, verify that all the parts are

included and check the nameplate to be sure the Liebert XDC voltage matches available utility

power.
Follow all local codes.

Enclosure

Cove r La tc h

Enclosure Cover La tch

Hazardous Voltage
Enclosure Cover

Hazardous Voltage
Enclosure Cover

Primary Disconnect
Switch

Status Lamp s

Us er Interface

Secondary Disconnect
Switch

SECONDARY

ELECTRICAL ENCLOSURE

PUMP SECTION

PRIMARY

ELECTRICAL ENCLOSURE

COMPRESSOR SECTION