Table 13, Recommended refrigerant line sizes for dcsl616 – Liebert Extreme Density Chiller XDC User Manual

Page 34

Advertising
background image

Piping and Filling with Refrigerant: R-134a and R-407c Circuits

28

Figure 28 DCSL616 piping connections—two refrigerant circuits connected for parallel flow

Table 13

Recommended refrigerant line sizes for DCSL616

Liebert XDC 160

Equivalent

Length, ft., (m)

*Hot Gas Line,

in.

Liquid Line, in.

50 (15)

1-1/8

7/8

100 (30)

1-1/8

1-1/8

150 (45)

1-3/8

1-1/8

200 (60)

1-3/8

1-1/8

* Double risers are required when hot gas vertical rise is 15 feet or
more (see 2.6 - Install Double Discharge Risers).

Traps * every 25 ft
(7.6m) of rise on hot
gas line only

Condenser Coil
(Circuit 1)

Condenser
Coil (Circuit 2)

Hot Gas/Discharge

Liquid/Return

Liq

uid

Re

tur

n F

rom

Co

nd

en

se

r

Standard
Piping
Assembly **

Rotalock
Valve **

1/4" (6.4mm)
Pressure Relief
Valve **

Sight Glass
Some Models Have
2 Sight Glasses

Lee-Temp
Receiver

Check
Valve

Head Pressure
Control with
Integral Check
Valve

Inverted Trap * on discharge
line to extend above base of
coil by a minimum of
7-1/2" (190mm)

Additional
Piping
Assembly **

DPN000937
Pg. 4, Rev 9

* * Components supplied by Liebert;
must be field-installed.

* Components are not supplied by Liebert
but are recommended for proper circuit
operation and maintenance.

Single XDC Circuit Shown

Field-Supplied Piping

Factory-Supplied Piping