Before beginning the installation of the Liebert XDC, read all instructions, verify that all the parts are

included, and check the nameplate to be sure the Liebert XDC voltage matches available utility power.
Follow all local codes.

Figure i

Model number nomenclature

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.

!

WARNING

Risk of unit falling over. Can cause death, injury and equipment damage.
The Liebert XDC is top-heavy. Use extreme caution and care when moving and installing this

unit.

!

CAUTION

Risk of piping and component rupture. Can cause injury or equipment damage. Closing

service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do

not close valves without following recommended procedures for repair, maintenance and

replacement of components. Install pressure relief valves in field piping that may become

isolated by service valves.

!

WARNING

Risk of refrigerant system explosion or rupture from overpressurization. Can cause injury,

death or equipment damage.
Installer must install a 400 psig pressure relief valve in each of the two R-407c refrigerant

circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and

the pressure relief valves.
For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a

notified body to the EU Pressure Equipment Directive.

!

CAUTION

Risk of contact with hot surfaces. Can cause burn injury. The compressors and refrigerant

discharge lines are extremely hot during unit operation. Allow sufficient time for the

compressors and refrigerant discharge lines to cool before working within the unit cabinet.

Use extreme caution and wear protective gloves and arm protection when working on or near

hot compressor and discharge lines.

NOTE
This document shall be used together with site specific documentation and documentation for

other parts of the system (heat rejection devices and cooling modules).

NOTE
Before any action that could cause a disturbance in the XD system’s cooling function is begun,

the facility manager MUST be informed. In addition, after the action is taken and the work is

finished, the facility manager MUST be informed.

A

Place holder

XD

C

160

1

Chiller

unit

Revision

level

Liebert

X-treme heat

Density system

Model size

Place holder

Example: XDC160AA– –1

A

A = 460V-3ph-60Hz

(voltage-phase-frequency)

M = 380/415-3ph-50Hz

Place holder