Table 19 compressor oil types, Table 19, Compressor oil types – Liebert Extreme Density Chiller XDC User Manual

Page 40: Caution

Advertising
background image

Checklist for Liebert XDC Startup

34

4.1

System Refrigerant Charges Over 35 lb. (15.9kg) Require Additional Oil

System charges over 35 lb. (15.9kg) require additional oil charge to be added. See Figure 30 for the

amount required for various charge levels.
Once the system has been fully charged with refrigerant, use a hand pump to add the additional oil at

the suction side of the system while the system is running.
The amount of oil added by field service must be recorded on a tag attached at the tandem the amount

added along with the date it was added. This will be documented on a tag located at the tandem com-

pressor and marked “Oil Added Field Service Record.”

Figure 30 Additional oil requirements for refrigerant charge

• Do not mix polyolester (POE) and mineral-based oils.
• Do not mix oils of different viscosities.

Consult Emerson or the compressor manufacturer if questions arise.

!

CAUTION

Risk of improper compressor lubrication. Can cause compressor and refrigerant system

damage.
Failure to use oil types, viscosities and quantities recommended by the compressor

manufacturer may reduce compressor life and void the compressor warranty. See oil types

specified in Table 19.

Table 19

Compressor oil types

Compressor Type

Refrigerant Type

R-22

R-407c

Carlyle Semi-Hermetic

Mineral Oil

POE OIL - ISO 68 Viscosity

Copeland Scroll and Digital Scroll

POE OIL - ISO 32 Viscosity

1. Use Carlyle Mineral Oil Totaline P903-2001, Witco Suniso 3GS or other Carlyle-approved oil.
2. Use Carlyle POE Totaline P903-1001, Castrol SW68 or other Carlyle-approved oil.
3. Use Copeland

®

POE Oil ULTRA 22CC, Mobil EAL Arctic 22CC, Copeland brand Ultra 22 CC, Copeland brand Ultra 32 CC,

Copeland brand Ultra 32-3MAF, Mobil EAL

Arctic 22 CC or Uniqema RL32-3MAF or other Copeland-approved oil.

140
130
120
110
100

90
80
70
60

50

40

30

20

10

0

0

100

300

200

400

Additional Oil Required Per Circuit, Ounces

Each circuit contains ZRT250KCE Tandem

XDC160 System Refrigerant Field Charge Per Circuit, Pounds