3 positioning the liebert xdc with floor stand, Positioning the liebert xdc with floor stand, Figure 9 – Liebert Extreme Density Chiller XDC User Manual

Page 15

Advertising
background image

Product Description

9

1.4.3 Positioning the Liebert XDC with Floor Stand

Install the Liebert XDC according to the site-specific documentation and secure the unit to the floor.
The Liebert XDC can be installed near a wall or another Liebert XDC. There must be at least 3 feet

(914mm) clearance in front of the Liebert XDC for service access. When the Liebert XDC is combined

with the optional water/glycol floor stand, Liebert recommends leaving 3 feet (914mm) of clearance on

the left side of the unit.
A Liebert XDC on a floor stand is 102 inches (2591 mm) high (see Figure 9). The unit can be raised or

lowered 1.5 inches (38.1 mm) with the leveling feet.

Figure 9

Dimensions and clearances for Liebert XDC on floor stand

78"

(1981mm)

102"

(2591mm)

24" Nominal

610 mm

Shaded areas indicate a recommended
cleareance of 36" (914mm) for component
access and water/glycol piping.