Piping and Filling with Refrigerant: R-134a and R-407c Circuits

18

Bypass Flow Controllers

To ensure the Liebert XDC pumps operate within the optimum range, some installations require one

or more bypass flow controller(s). These devices are added to the field piping, and simulate the flow of

additional cooling modules.
Each bypass flow controller should be installed with one shutoff valve to allow the controller to be dis-

abled when cooling modules are added to a Liebert XD system.
If bypass flow controllers are required, they should be connected between the main supply and the

main return lines of the field piping. The connection points to the main supply and return lines should

be in a convenient and accessible location between the Liebert XDP/Liebert XDC and the first Liebert

XD module in the circuit. See Figures 20 and 21 for piping details of the bypass flow controller.
Refer to Table 5 to determine the number of bypass flow controllers needed, based on the total nomi-

nal cooling capacity of the cooling modules in each Liebert XD system.

Figure 20 Bypass flow controller details, dimensions

Figure 21 Bypass flow controller arrangement

Table 5

Bypass flow controllers for a Liebert XDC-based system

Cooling Modules -

Cumulative Model Size

Required Number

of Bypass Flow Controllers

Liebert XDC

32 to 63

N/A

64 to 95

2

96 to 127

1

128 to 160

0

7/8”

(22mm) ID

4”

(102mm)

Return

Main

7/8" Refrigerant Grade
Full Port Ball Valve
Field-Supplied and Field-Installed

Supply

Main

Bypass Flow Controller
(Field-Installed)

Flow Direction