2 setpoints, Min temp sp, Hi air temp – Liebert Extreme Density Chiller XDC User Manual

Page 44: Lo air temp, Setpoints, Table 21

Advertising
background image

Microprocessor Control

38

5.3.2 SETPOINTS

Selecting SETPOINTS from the Main Menu will reveal the following menu items:

To reach the SETPOINTS menu:
1. Press the MENU button.
2. Press ENTER when the SETPOINTS menu is displayed.
3. Use the up and down arrow keys to move through the menu and view the setpoints.
To change a setpoint, follow the steps above, then:
1. Press the ENTER key to change a setpoint. (The control will ask for a setpoint password if

passwords are enabled. Use the up and down arrow keys and ENTER key to enter the three-digit

password when prompted.)

2. Use the up and down arrow keys to change the setpoint.
3. Then, press ENTER to accept the new setpoint. When finished, press the ESC key two to three

times to return to the main display.

The user setpoints and ranges are:

MIN TEMP SP

This setpoint is used to keep the room temperature above the setpoint. The Liebert XDC can lower

the room temperature too much depending on the room dew point and load. This setpoint will back off

the cooling to keep the room temperature above this temperature, see 5.3.1 - Viewing or Changing

Settings.

HI AIR TEMP

This is the temperature at which the HIGH REMOTE TEMP and HIGH LOCAL TEMP alarms will

be activated, see 5.3.1 - Viewing or Changing Settings.

LO AIR TEMP

This is the temperature at which the LOW REMOTE TEMP and LOW LOCAL TEMP alarms will be

activated, see 5.3.1 - Viewing or Changing Settings.

Table 21

Setpoint functions, default values and allowable ranges

Menu Item

Function

Default

Range

MIN TEMP SP *

Minimum room temperature setpoint

72 (22)

50-80 (10-27)

HI AIR TEMP

High room air temperature alarm

80 (27)

35 to 95 (2-35)

LO AIR TEMP

Low room air temperature alarm

55 (13)

35 to 95 (2-35)

* For optimal cooling performance, the minimum temperature setpoint should be at least 1-2° below the expected temperature at

the remote sensor, which may require additional consideration of the remote sensor location or minimum temperature setting.
If the minimum temperature setpoint is set above the typical remote temperature sensor reading, this will reduce the Liebert
XD cooling output and, in extreme cases, cause erratic Liebert XD performance.

NOTE
Setpoints and system setup parameters are kept in non-volatile memory.

NOTE
This is not a true room temperature setpoint. The Liebert XDC will try to cool as much as

possible. If it is able to cool the room to this setpoint, it will back off its cooling capability to try

to keep the room temperature at or above this setpoint, but the Liebert XDC has no heaters, so it

cannot warm the room.

Advertising