Troubleshooting

51

Room becomes

too warm

Liebert XDC is off.

Check status of the Liebert XDC at the user interface. Turn

system On at I/O button if system is Off.

High dew point

Check temperature and relative humidity (RH) of room.

Lower RH setpoint if necessary to lower dew point. At normal

room temperature of 68°F (20°C), the RH should be set to

50% or lower.

Liebert XD cooling modules are Off.

Check Liebert XD cooling modules to make sure that they are

On before starting the Liebert XDC.

Minimum room temperature setpoint

is too high.

Check the setpoint by following instructions in 5.3.2 -

SETPOINTS.

Incorrect location of temperature-

humidity senors

Place the sensor on the return air side of the primary air

mover (I.e., Liebert Deluxe System 3). Do not install the

sensor near unsealed doors, windows, and similar areas.

Pipe rattle

Loose pipe connections

Check pipe connections.

Actuator motors

(if applicable)

No 24VAC power to motor

Check for 24VAC between P2-1 and P2-4.

No signal from control

Check 24VAC at P22-1 (close) or P22-3 (close).

Motor not operating

Unplug P22 completely off of the board. Jumper P22-5 to P2-

4 for grounding, then jumper P22-1 to P2-1 to drive close.

Remove jumper to close, and then jumper P22-3 to P2-1 to

drive open. If motor fails to work, replace it.

Motor burnout

Check control panel for welded

contactor contacts or welded

overload contacts

Replace defective components.

Main 24VAC

fuse trips

Shorts or loose connections

Check the wiring connections of the 24VAC circuit.

Faulty circuit board

Replace the circuit board.

Unstable pump

operation

R-134a pump loop is overcharged

While pump is running R-134a receiver level must be within

recommended levels (see Figure 31).

Table 24

Liebert XDC troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy