Figure 31 system r-134a liquid level – Liebert Extreme Density Chiller XDC User Manual

Page 41

Advertising
background image

Checklist for Liebert XDC Startup

35

The Liebert XDC system is now ready to be turned ON.
1. Turn On all fans of the Liebert XD cooling modules.
2. Turn the Liebert XDC On via user interface (I/O button). Allow the system to attempt to start for

at least 2 minutes.
If the Liebert XDC pump cannot maintain flow and continues to switch over due to starting diffi-

culties, proceed to Step 4 and refer to the troubleshooting section of the Liebert XDC user man-

ual.

3. If constant flow is established, wait until the Liebert XDC has been operating 10-15 minutes, then

verify that the refrigerant level in the receiver sight glass is between the second and third level

(see Figure 31). Add or remove charge as indicated by sight glass level.

4. Check pressure differential functionality:

The Liebert XDC system should be On. If it is Off:
a. Turn On the Liebert XD cooling module fans
b. Turn the Liebert XDC On via user interface (I/O button).

If there is no “Loss of Flow” alarm present—This suggests that there is flow. Test the

pressure differential by closing the ball valve on either the suction line or discharge line to

stop the flow.
This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has

opened on low pressure (below 6 psi; 41 kPa; 0.41 bars).
If there is a “Loss of Flow” alarm present—This suggests that there is no flow. Verify

that this is correctly annunciated by looking at the sight glass in the receiver. If a true no-flow

condition exists, the level will not move.
However, if there is flow, but the differential reading is faulty, the level will slowly

drop, indicating flow, while the loss of flow alarm is annunciated.
Check the pressure differential physically by making sure that the electrical connections are

properly connected. Then check the pressure differential electrically by making sure that the

unit has 24VAC across it.

Figure 31 System R-134a liquid level

Operation above sight glass #3 can
make the system operate erratically
and reduce cooling capacity - Reduce
charge to recommended level.

Recommended operating level

Acceptable operating level

Operation below sight glass #1 may
cause loss of flow or cooling. Add
charge to reach recommended level.

For lightly loaded systems,
the recommended operating
level is sight glass #2.

Sight Glasses 1, 2 & 3

Advertising