Installation, Rigid pipe venting arrangements, Inst alla tion – Regency P33 SunriseTM P33S-LP4 User Manual
Page 19: Vertical terminations (propane & natural gas)

Regency P33 Sunrise
TM
Gas Fireplace
19
INST
ALLA
TION
• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles.
Note: Must use optional rigid pipe adapter when using rigid vent systems (Part # 510-994).
RIGID PIPE VENTING ARRANGEMENTS
Vertical Terminations
(Propane & Natural Gas)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using one 90
o
elbow, with
rigid pipe vent systems for Propane and Natural Gas.
Minimum
8
'6”
(2.6m)
Maximum
35
’(10.6m)
35
8
10
12
14
16
18
20
22
24
26
28
30
6
0
2
4
2
0
6
4
Horizontal (Feet)
Floor
2
0
6
10
4
8
12
V
ertical
Height
(Feet)
Minimum
8
'6”
(2.6m)
Maximum
27
’(8.2m)
Horizontal (Feet)
Min. 12” (305mm)
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0
2
4
6
Max. 10’ (3m)
(centerline to centerline)
Floor
INSTALLATION