Installation, Rigid pipe venting arrangements, Inst alla tion – Regency P33 SunriseTM P33S-LP4 User Manual

Page 19: Vertical terminations (propane & natural gas)

Advertising
background image

Regency P33 Sunrise

TM

Gas Fireplace

19

INST

ALLA

TION

• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles.

Note: Must use optional rigid pipe adapter when using rigid vent systems (Part # 510-994).

RIGID PIPE VENTING ARRANGEMENTS

Vertical Terminations

(Propane & Natural Gas)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using one 90

o

elbow, with

rigid pipe vent systems for Propane and Natural Gas.