GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.

The manifold pressure is controlled by a
regulator built into the gas control, and should
be checked at the pressure test point.

Note: To properly check gas pressure,

both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.

1) Make sure the valve is in the "OFF"

position.

2) Loosen the "IN" and/or "OUT" pressure

tap(s), turning counterclockwise with a
1/8" wide fl at screwdriver.

3) Attach manometer to "IN" and/or "OUT"

pressure tap(s) using a 5/16" ID hose.

4) Light the pilot and turn the valve to "ON"

position.

5) The pressure check should be carried out

with the unit burning and the setting should
be within the limits specifi ed on the safety
label.

6) When fi nished reading manometer, turn

off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
fl at screwdriver. Note: Screw should be
snug, but do not over tighten.

Incorrect fl ame pattern will have small,
probably yellow fl ames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.

HIGH ELEVATION

This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.

PILOT ADJUSTMENT

Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames:
1 fl owing around the thermopile, 1 around
the thermocouple and 1 fl owing across the
burner (it does not have to be touching the
burner).

Note: If

you have an incorrect fl ame

pattern, contact your FPI dealer for further
instructions.

P33S-NG4 System Data

Conversion Kit# 434-970 (NG to LP)

For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:

#47

Max. Input Rating 17,000 Btu/h
Min. Input Rating

12,000 Btu/h

Supply Pressure min.5.0"

w.c.

Manifold Pressure
(High)

3.5"+/- 0.3" w.c.

P33S-LP4 System Data

For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:

#56

Max. Input Rating 15,500 Btu/h
Min. Input Rating

12,000 Btu/h

Supply Pressure min.11.0"

w.c.

Manifold Pressure
(High)
10"+/-

0.4"w.c.

S.I.T. VALVE DESCRIPTION

1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot

Adjustment

4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point