Installation, Clearances, Inst alla tion – Regency P33 SunriseTM P33S-LP4 User Manual

Page 9

Advertising
background image

Regency P33 Sunrise

TM

Gas Fireplace

9

INST

ALLA

TION

INSTALLATION

Caution Requirements

The top, back and sides of the fi replace are defi ned by

standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials are not

adhered to. It is of greatest importance that this fi replace and vent

system be installed only in accordance with these instructions.

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.

C

Clearance:

Dimension

Measured From:

A: *Front Floor Clearance (min.)

12" (304mm)

Underside of Unit

B: *Sidewall (on one side)

7-1/2" (241mm)

Side of Unit

C: *Ceiling
(room and/or alcove)

30" (889mm)

Top of Unit

D: Alcove Width

48" (1219mm)

Sidewall to Sidewall (Minimum)

E: Alcove Depth

36" (914mm)

Front to Back Wall (Maximum)

B

C

Close to Ceiling

Flue Clearances

Horizontal - Top

2-1/2"

Horiztonal - Side

1-1/2"

Horiztonal - Bottom

1-1/2"

Vertical (Flex Vent)

1-1/2"

Vertical (Rigid)

1-1/4"

*Note: All measurements are from the top/side of the unit, not optional front.