2 contents of the product, 3 installation – Toshiba VF-S11 User Manual

Page 10

Advertising
background image

E6581160

9

1

1.2

Contents of the product

Explanation of the name plate label. Always shut power off first then check the ratings label of inverter held in a
cabinet.

Type

Form

V F S 11 S - 2 0 0 7 P L E - W N - A 2 2

Model name

TOSVERT

VF-S11series

Number of

power phases

S: single-phase

None:

three-phase

Applicable motor

capacity

002 : 0.2kW
004 : 0.4kW
005 : 0.55kW
007 : 0.75kW
015 : 1.5kW
022 : 2.2kW
037 : 3.7kW
055 : 5.5kW
075 : 7.5kW
110 : 11kW
150 : 15kW

Additional functions I

None: No filter inside

M: Built-in basic filter

L: Built-in

high-attenuation

EMI filter

Operation panel

P: Provided

Default interface

logic*

WN, AN : Negative
WP

: Positive

Special specification code

A††:††is the number

Input (AC) voltage

2 : 200V to 240V
4 : 380V to 500V
6 : 525V to 600V

Additional function II

None: Standard product
E: Enclosed type
U: Open type
R: With a built-in RS-485

circuit board

* This code represents the factory default logic setting. You can switch from one input/output logic to the other using

slide switch SW1.

1.3

Installation

Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation.
If you are installing more than one inverter, the separation between inverters should be at least 5 centimeters,
and they should be arranged in horizontal rows. If the inverters are horizontally arranged with no space
between them (side-by-side installation), peel off the ventilation seals on top of the inverter. It is necessary to
decrease the current if the inverter is operated at over 50°C.

••••Standard installation

••••Side-by-side installation

5 cm or more

5 cm or more

10 cm or more

10 cm or more

Remove seals on top

VFS11

VFS11

VFS11

VFS11

10 cm or more

10 cm or more

The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:

Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.