Qtable of output terminal functions 3 – Toshiba VF-S11 User Manual

Page 70

Advertising
background image

E6581160

69

7

Q

Table of output terminal functions 3

Function

No.

Code

Function

Action

35

FCVIBN

Inversion of frequency VIB selection

Inversion of FCVIB

36

FLR

Fault signal (put out also at the time of a retry)

ON: When inverter trips or retries
OFF: When inverter does not trip or retry

37

FLRN

Inversion of failure signal (put out also at the time
of a retry)

Inversion of FLR

38

OUT0

Specified data output 1

ON: Specified data from remote control FA50:

BIT0= 1

OFF: Specified data from remote control FA50:

BIT0= 0

39

OUT0N

Inversion of specified data output 1

Inversion of OUT0 setting

40

OUT1

Specified data output 2

ON: Specified data from remote control FA50:

BIT1= 1

OFF: Specified data from remote control FA50:

BIT1= 0

41

OUT1N

Inversion of specified data output 2

Inversion of OUT1 setting

42

COT

Cumulative operation time alarm

ON: Cumulative operation time is equal to or

longer than H

OFF: Cumulative operation time is shorter than

H

43

COTN

Inversion of cumulative operation time alarm

Inversion of COT

44

LTA

Parts replacement alarm

ON: Calculation for parts replacement time is

equal to or longer than the preset time

ON: Calculation for parts replancement time is

shorter than the preset time

45

LTAN

Inversion of replacement alarm

Inversion of LTA

46

BR

Braking sequence output

ON: Braking retention signal
OFF: Braking release signal

47

BRN

Inversion of braking sequence output

Inversion of BR

48

LI1

F terminal input signal

ON: The signal input to F terminal is ON
OFF: The signal input to F terminal is OFF

49

LI1N

Inversion of F terminal input signal

Inversion of LI1

50

LI2

R terminal input signal

ON: The signal input to R terminal is ON
OFF: The signal input to R terminal is OFF

51

LI2N

Inversion of R terminal input signal

Inversion of LI2

52

PIDF

Signal in accordance of frequency command

ON: Frequency commanded by HOQF or

H

and that by VIA show the same

value.

OFF: Frequency commanded by HOQF or

H

and that by VIA show different

values.

53

PIDFN

Inversion of signal in accordance of frequency
command

Inversion of PIDF setting

54

MOFF

Undervoltage detection

ON: Undervoltage detected
OFF: Other than undervoltage

55

MOFFN

Inversion of undervoltage detection

Inversion of MOFF

56-253

Disabled

Invalid settings, always OFF (ignored)

Invalid settings, always OFF (ignored)

254

AOFF

Always OFF

Always OFF

255

AON

Always ON

Always ON