SINK (Negative) logic/SOURCE (Positive) logic (When an external power supply
is used)

The PLC terminal is used to connect to an external power supply or to insulate a terminal from other input
or output terminals. As for input terminals, turn the SW1 slide switch to the PLC position.

Examples of connections when an external power supply is used>

Sink (Negative) logic

Inverter

PLC

F

Programmable
controller

Common

Output

Input

24V

DC

Output

F

Output

Input

24V

DC

Output

OUT

NO

24V

DC

Input

Common

Inverter

Programmable
controller

Slide switch SW1:PLC

Slide switch SW1:PLC

PLC

Common

24V

DC

OUT

Common

NO

Input

Source (Positive) logic

Q

Selecting the functions of the VIA and VIB terminals between analog input and
contact input

The functions of the VIA and VIB terminals can be selected between analog input and contact input by
changing parameter settings (H). (Factory default setting: Analog input)
When using these terminals as contact input terminals in a sink logic circuit, be sure to insert a resistor
between the P24 and VIA terminals or between the P24 and VIB terminals. (Recommended resistance:
4.7K

Ω-1/2W)

When using the VIA terminal as a contact input terminal, be sure to turn the VIA switch to the V position. If
no resistor is inserted or the VIA slide switch is not turned to the V position, contact input will be left always
ON, which is very dangerous.
Switch between analog input and contact input before connecting the terminals to the control circuit
terminals. Otherwise the inverter or devices connected to it may be damaged.