E6581160

34

4

Q

How to use the history function

Key operated

LED display

Operation



Displays the operation frequency (operation stopped).
(When standard monitor display selection H= [Operation
frequency])

CWJ

The first basic parameter “CWJ” (history function) is displayed.

CEE

The parameter that was set or changed last is displayed.



Press the ENTER key to display the set value.



Press the key and key to change set value.



⇔CEE

Press the ENTER key to save the changed value. The parameter
name and the programmed value will flash on and off alternately.

****

Use the same steps as those given above to display parameters that
you want to search for or change setting with the key and key.

JGCF

(GPF)

JGCF

: First historic record

GPF

: Last historic record

Parameter

display

CWJ

HTH



Press the MODE key to return to the parameter setting mode
“CWJ.”
After that you can press the MODE key to return to the status
monitor mode or the standard monitor mode (display of operation
frequency).

Note) Parameter f700 (Prohibition of change of parameter settings) is not displaied in this “auh”.

4.2.5 Parameters that cannot be changed while running

For safety reasons, the following parameters have been set up so that they cannot be reprogrammed while
the inverter is running. Stop operation (“0.0” or “off” is displayed) before changing parameter settings.

[Basic parameters]

CW

, CW, CW, EOQF*, HOQF*, V[R, HJ, XN, XNX, RV

[Extended parameters]

H

, H

∼H, H∼H, H, H, H, H∼H, H,

H

∼H, H, H∼H, H∼H, H, H, H, H,

H

, H, H, H

∼H

The setting of any parameter other than the above can be changed even during operation.
Keep in mind, however, that when the parameter H (prohibition of change of parameter settings) is set to 
(prohibited), no parameters can be set or changed.

* Set H, cmod and fmod can be changed while the inverter is running.