9. Before making a service call

- Trip information and remedies

9.1

Trip causes/warnings and remedies

When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba dealer.

[Trip information]

Error code

Failure code

Problem

Possible causes

Remedies

QE
QER

0001
0025

Overcurrent during
acceleration
Overcurrent flowing
in element during
acceleration

• The acceleration time CEE is too short.

• The V/F setting is improper.

• A restart signal is imput to the rotating

motor after a momentary stop, etc.

• A special motor (e.g. motor with a small

impedance) is used.

• Increase the acceleration time CEE.

• Check the V/F parameter.

• Use H (auto-restart) and H

(ride-through control).

• Adjust the carrier frequency H.

• Set the carrier frequency control mode

selection parameter f316 to 1 or 3
(carrier frequency decreased
automatically).

QE
QER

0002
0026

Overcurrent during
deceleration
Overcurrent flowing
in element during
decelearion

• The deceleration time FGE is too short.

• Increase the deceleration time FGE.
• Set the carrier frequency control mode

selection parameter f316 to 1 or 3
(carrier frequency decreased
automatically).

QE
QER

0003
0027

Overcurrent during
constant speed
operation
Overcurrent flowing
in element during
operation

• The load fluctuates abruptly.
• The load is in an abnormal condition.

• Reduce the load fluctuation.
• Check the load (operated machine).

• Set the carrier frequency control mode

selection parameter f316 to 1 or 3
(carrier frequency decreased
automatically).

ER
ER
ER

0025
0026
0027

Ground fault trip
Arm overcurrent at
start-up
(for 11 and 15 kW
models only)

• A current leaked from an output cable or

the motor to ground.

• A main circuit elements is defective.

• Check cables, connectors, and so on for

ground faults.

• Make a service call.

QEN

0004

Overcurrent (An
overcurrent on the
load side at start-up)

• The insulation of the output main circuit or

motor is defective.

• The motor has too small impedance.

• A 11 or 15 kW model was started,

although a current is leaked from an
output cable or the motor to ground.

• Check the cables and wires for defective

insulation.

• When using a 11 or 15 kW model, check

cables, connectors, and so on for ground
faults.

QEC

0005

Arm overcurrent at
start-up

• A main circuit elements is defective.

• Make a service call.

*
GRJ

0008

Input phase failure

• A phase failure occured in the input line of

the main circuit.

• The capacitor in the main circuit lacks

capacitance.

• Check the main circuit input line for phase

failure.

• Enable H (input phase failure

detection).

• Check the capacitor in the main circuit for

exhaustion.

*
GRJQ

0009

Output phase failure

• A phase failure occurred in the output line

of the main circuit.

• Check the main circuit output line, motor,

etc. for phase failure.

• Enable H (Output phase failure

detection).

* You can select a trip ON/OFF by parameters.