Communication parameters – Toshiba VF-S11 User Manual

Page 63

Advertising
background image

E6581160

62

7

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

E6581158

H

0710

Standard monitor

display selection

-

-

0: Operation frequency (Hz/free unit)
1: Frequency command (Hz/free unit)
2: Output current (%/A)
3: Inverter rated current (A)
4: Inverter load factor (%)
5: Output power (%)
6: Frequency command after PID

control (Hz/free unit)

7: Optional item specified from an

external control unit

0

6.21.5

H

0719

Canceling of

operation

command when

standby terminal

(ST) is turned off

-

-

0: Operation command canceled

(cleared)

1: Operation command retained

1

6.21.6

H

0721

Panel stop pattern

-

-

0: Slowdown stop
1: Coast stop

0

6.21.7

H

0730

Prohibition of

frequency setting

on the operation

panel (HE)

-

-

0: Permitted
1: Prohibited

0

H

0733

Panel operation

prohibition

(RUN/STOP keys)

-

-

0: Permitted
1: Prohibited

0

H

0734

Prohibition of

panel emergency

stop operation

-

-

0: Permitted
1: Prohibited

0

H

0735

Prohibition of

panel reset

operation

-

-

0: Permitted
1: Prohibited

0

H

0736

Prohibition of

change of EOQF

/ HOQF during

operation

-

-

0: Permitted
1: Prohibited

1

6.21.1

• Communication parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

E6581158

H

0800

Communication

rate

-

-

0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps

3

H

0801

Parity

-

-

0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)

1

H

0802

Inverter number

-

1/1

0-255

0

H

0803

Communication

error trip time

s

1/1

0: (disabled)
1-100

0

H

0805

Communication

waiting time

s

0.01/0.01

0.00-2.00

0.00

H

0806

Setting of master

and slave for

communication

between inverters

-

-

0: Slave (0 Hz command issued in

case the master inverter fails)

1: Slave (Operation continued in case

the master inverter fails)

2: Slave (Emergency stop tripping in

case the master inverter fails)

3: Master (transmission of frequency

commands)

4: Master (transmission of output

frequency signals)

0

6.22