2 display of trip information, 1 trip code display – Toshiba VF-S11 User Manual

Page 41

Advertising
background image

E6581160

40

5

5.2

Display of trip information

5.2.1 Trip code display

If the inverter trips, an error code is displayed to suggest the cause. Since trip records are retained, information
on each trip can be displayed anytime in the status monitor mode.
For the kinds of causes that can be indicated in the event of a trip, see section 9.1.

5.2.2 Display of trip information at the occurrence of a trip

At the occurrence of a trip, the same information as that displayed in the mode described in 5.1.1, "Status monitor
under normal conditions," can be displayed, as shown in the table below, if the inverter is not turned off or reset.
To display trip information after turning off or resetting the inverter, follow the steps described in 5.1.2, "Display of
detailed information on a past trip."

Example of call-up of trip information

Item displayed

Key

operated

LED

display

Communic
ation No.

Description

Cause of trip

QR

Status monitor mode (The code blinks if a trip
occurs.)
The motor coasts and comes to a stop (coast stop).

Parameter setting
mode

CWJ

The first basic parameter “CWJ” (history function)
is displayed.

Direction of
rotation

HT

-H

FE01

The direction of rotation at the occurence of a trip
is displayed. (HTH: forward run, HTT:
reverser run).

Operation
frequency
command

H

FE02

The operation frequency command value (Hz/free
unit) at the occurrence of a trip is displayed.

Load current

E

FE03

The output power of the inverter at the occurrence
of a trip (%/A) is displayed.

Input voltage

[

FE04

The inverter input (DC) voltage (%/V) at the
occurrence of a trip is displayed.

Output voltage

R

FE05

The output voltage of the inverter at the
occurrence of a trip (%/V) is displayed.

Torque

SQ

FE18

The torque at the occurrence of a trip (%) is
displayed.

Torque current

Y

FE20

The torque current (%/A) at the occurrence of a
trip is displayed.

Inverter load factor

N

FE27

The inverter load factor (%) at the occurrence of a
trip is displayed.

PBR cumulative
load factor

T

FE25

The cumulative load factor (%) of the resistor at
the occurrence of a trip is displayed.

Input power

k

FE29

The inverter input power (kW) at the occurrence of
a trip is displayed.

Output power

J

FE30

The inverter output power (kW) at the occurrence
of a trip is displayed.

Operation
frequency

Z

FE00

The inverter output frequency (Hz/free unit) at the
occurrence of a trip is displayed.

(Continued overleaf)

MO

MO

MO

MODE

DE

DE

DE

MO

MO

MO

MODE

DE

DE

DE

Note 3

Note 2

Note 1