Toshiba VF-S11 User Manual

Page 61

Advertising
background image

E6581160

60

7

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

E6581158

H

0609

Small current

detection current
hysteresis

%

1/1

1-20

10

H

0610

Small current
trip/alarm

selection

-

-

0: Alarm only
1: Tripping

0

H

0611

Small current
detection current

%

(A)

1/1

0-100

0

H

0612

Small current

detection time

s

1/1

0-255

0

6.19.7

H

0613

Detection of
output short-circuit
during start-up

-

-

0: Each time (standard pulse)
1: At start-up (only one time after

power is turned on)

(standard pulse)

2: Each time (short-time pulse)
3: At start-up (only one time after

power is turned on)

(short-time pulse)

0

6.19.8

H

0615

Over-torque

trip/alarm
selection

-

-

0: Alarm only

1: Tripping

0

H

0616

Over-torque
detection level

%

1/1

0-250

150

H

0618

Over-torque
detection time

s

0.1/0.1

0.0-10.0

0.5

6.19.9

H

0619

Over-torque
detection level

hysteresis

%

1/1

0-100

10

6.19.9

H

0621

Cumulative
operation time

alarm setting

100

Time

0.1/0.1

(=10 hours)

0.0-999.9

610

6.19.10

H

0626

Over-voltage stall
protection level

%

1/1

100-150

*1

6.13.5

H

0627

Undervoltage

trip/alarm
selection

-

-

0: Alarm only

(detection level below 60%)

1: Tripping

(detection level below 60%)

2: Alarm only

(detection level below 50%,
DC reactor necessary)

0

6.19.12

H

0633

Trip at VIA low

level input mode

1/1

0: Disabled, 1-100

0

6.19.13

H

0634

Annual average
ambient

temperature (parts
replacement
alarms)

-

-

1: -10 to +10

°C

2: 11-20

°C

3: 21-30

°C

4: 31-40

°C

5: 41-50

°C

6: 51-60

°C

3

6.19.14

*1 : Default values vary depending on the capacity. See the table of 64.